Flame Monitoring Device F130I

  • Flame monitoring device for main and Ignition flame ;
  • Ionization based flame monitoring;
  • Approved for continuous operation with ionization;
  • Approved for intermittent operation with UV tubes and LDR sensors;
  • Two-channel system with electronic self-monitoring;
  • LED based status display;
  • Plug-in module for top hat rail assembly;
  • Designed for installation in control panels;
  • No modifications needed for country-specific mains frequencies
  • SIL 3 as per DIN EN 61508-1-7 
Technical Data
Power supply voltage:

230 VAC +10 % -15 %
120 VAC +10 % -20 %

Flame and signal contact: Floating
Mains frequency: 47 Hz … 63 Hz
Safety time “operation”: tVoff ≤ 1 s
Mode of operation: Continuous operation
Protection class: IP20
Operating temperature: -20 °C … +60 °C
Dimensions: 114 x 120 x 45 mm (TxHxB)
Weight: 0,5 kg

Approvals:

EC type-examination certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012
  • DIN EN 13611:2011
  • DIN EN 60730-2-5:2011
  • DIN EN 60730-1:2012
  • DIN EN 746-2:2011 for process burners

 

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

 

CE Declaration of Confomity

  • 2014/68/EU (Pressure Equipment Directive)
  • 2009/142/EC (Gas Appliance Directive)
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)

 

ANSI / UL 1998, 2nd Edition in Combination with ANSI / UL 372, 5th Edition and UL353, 5th Edition

 

 
Purpose

The F130I flame monitoring device is LAMTEC’s new safety system, designed specially for monitoring ignition and main flames.The F130I flame monitoring device by LAMTEC provides operators of industrial firing systems and power plants with a reliable high-tech device for flame monitoring.

The F130I uses ionisation to monitor the flame. Optical flame sensors can also be connected to the device. The F130I flame monitoring device is particularly impressive when used for more demanding monitoring requirements, such as monitoring in firing systems with single burner flames. The ionisation-based F130I flame monitoring device has been approved for permanent operation.

The evaluation device may only be operated with the approved flame sensors. The F130I is not designed for the direct switch-off fuel valves. The subsequent signalprocessing must be carried out in the control system, which is adapted to suit the firing system in question.

Selection criteria
Sensor type F130I input For fuel Continuous operation Wavelength range
UV tubes UV Gas / Oil No 190 … 270 nm
LDR, visible LDR Oil No 450 … 800 nm
LDR, visible LDR Oil No 400 … 800 nm
Ionisation ION Gas Yes